K & W Services logo - the generator specialists  |  home | about us | what we do | contact us |
|  Generator Sales  | Generator Servicing  |  Generator Hire  |  Generator Leasing  |  Installation  |  Diesel Generators  |  Portable Power  | 
generator specifications

AT V300 KVA

Standby Power @ 50Hz -
264 kW / 330 KVA
Prime Power @ 50Hz -
240 kW / 300 KVA

Engine - Volvo TAD941GE
Charge Alternator 24V Governor: Elec
Alternator - Marelli MJB315SA
Single bearing alternator IP 23, insulation class H/H
Radiator 50°C (122°F) max, air inlet with coolant cap
Skid and vibration isolators
Dry type air filter
Main line circuit breaker
Microprocessor control panel
24V battery, rack and cable
Industrial silencer (loose)
User manual
Factory test certificate
Voltage Hz Phase Power Factor Standby Amps Standby ratings kw/KVA Prime ratings kw/KVA
415/240 50 3 0.8 495 264/330 240/300
400/230 50 3 0.8 495 264/330 240/300

RRP: Prime power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. A 10% overload capability is available for a period of 1 hour within a 12 hour period of operation, in accordance with ISO 3046-1

ESP: The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is not allowed.

Large diesel generator dimensions

Type Length (mm) Width (mm) Height (mm) Weight (kg) Tank (L)
openset 3200 1100 1700 2637 482
enclosure 3969 1337 1950 3347 544

Engine Data

Manufacturer/Model - Volvo TAD941GE
No of Cylinder / Configuration - 6 - inline
Displacement - 9.36 L
Bore and stroke - 120 mm x 138 mm
Compression Ratio - 17.4:1
Rated RPM - 1500 rpm
Governor: type - Electronic
Engine gross power - 323 kWm
Aspiration - Turbocharged and intercooled

Exhaust System

Exhaust gas flow - 52.2 m3/min
Exhaust temperature - 539°C

Fuel Consumption

100% - 57.1 L/h
75% - 44.6 L/h
50% - 32.9 L/h

Oil System

Lubrication oil system - 30 L

Air Intake

Combustion air flow - 19.6 m3/min
Cooling air flow - 258 m3/min

Coolant Systems

Coolant capacity - 24 L
Cooling system - Water

Alternator Specifications

Manufacturer/Type - MArelli MJB315SA
Number of phase - 3
Power factor - 0.8
Pole: number - 4
No of bearing - Single
Insulation class - H
Voltage regulation - +/- 0.5%
Excitation system - AVR (Automatic Voltage Regulator), Brushless
No of leads - 12
Degree of protection - IP 23
Total harmonic content (no load) - <2%
Voltage output - 230 / 400 VAC
Efficiency - 93.4%

Large diesel generator control panelThe control system used for this system is based upon the Deep Sea Electronics DSE7210 Digital Auto Start controller. This provides for the manual and automatic remote start of the generator and contains the following features:

  • Real time clock for improved event and preformance monitoring
  • 132 x 64 pixel LCD display
  • Multiple date and time maintenance scheduler
  • Five key menu navigation
  • Operated via Start, Stop, Auto and Manual soft touch membrane buttons on the front panel
  • Coolant temperature with high temperature alarm and shutdown
  • Coolant temperature low warning
  • Oil pressure with low pressure alarm and shutdown
  • Oil temperature, engine operating hours, battery charge volts and amps
  • Volts, with Under/Over volts protection
  • Amps, with Over current protection
  • Frequency, kW, KVA, Power Factor
  • Automatic cool-down timer function

Large Diesel Generator enclosedThe acoustic enclosure is suitable for operation in harsh outdoor environments whilst providing excellent security and acoustic performance. The steel canopy and baseframe is of fully welded construction with a two-pack polyurethene egg-shell finish in RAL9001 white.

Acoustically, the canopy is designed to meet the requirements of EU Legislation 2000/14/EC, achieved by extensive use of rock wool and perforated zintec steel lining, together with efficient management of cooling air. Exhaust noise is minimised by a unique high performance exhaust silencer, mounted within the baseframe.

A steel bunded fuel tank is situated inside the baseframe to allow 8 hours running of the generator at 75% load. Also integrated within the baseframe are filler, guage and accessory points.

Other key features are:

  • Lifting and holding down points on baseframe
  • 4 no. eye lifting hooks
  • Emergency stop button relocated to canopy exterior
  • External service access panels
  • Heavy duty locks on all doors for total security
  • Weather cap on exhaust discharge
  • Side opening doors with retainers for good service access

Engine and Radiator

  • Heat shield protection
  • Oil drain extension
  • Heavy duty oil filter
  • Lube oil drain pump
  • Radiator core guard
  • Battery charger
  • Block header

Alternator

  • Anti condensation heater
  • Enforced impregnation
  • Oversized alternator

Enclosure

  • M227
  • 85dba @ 1m silent canopy

Control Panel

  • Paralelling system
  • Remote annunciator
  • Co-map / Deepsea
  • Key panel start

Exhaust

  • Residential silencer
  • Flexible exhaust connection

Fuel

  • 24 hour day tank
  • Bulk fuel tank connections
  • Water seperator fuel filter
For ALL your generator requirements - contact the specialists
Site managed by Creative Munkys
|  Generator Sales  | Generator Servicing  |  Generator Hire  |  Generator Leasing  |  Installation  |  Diesel Generators  |  Portable Power  |